Copyright: Wuhan Nanxing Power Technology Co., Ltd.  鄂ICP备06008607号
Website:300.cn  Wuhan

  • 武汉南星电力科技有限公司
  • 武汉南星电力科技有限公司
  • 武汉南星电力科技有限公司

NDBYC-2000 Transformer on-load switch tester

Profile information:
basic information
Detailed parameters
Categories:
Transformer detection class
heat
number:
- +
没有此类产品
Product description
  Reference standard: GB/T 10584-1989, DL/T846.8-2004.
 
  Features:
  ● Test Y0, Y, △ type transformer, the resistance value is directly displayed without conversion;
  ● Humanized data analysis can automatically find faults in the middle of the waveform and make marks;
  ● The display of the waveform is automatically adjusted according to the data returned from the sample and the amplitude of the time;
  ● It can be tested with or without windings;
  ● Four-terminal wiring method, providing high-precision resistance measurement without wire compensation;
  ● Continuous testing can be carried out in the middle of the test to save time for transformer power failure.
 
  The main parameters:
 
 Three-phase constant current source
1A File; 0.2A File
Port maximum voltage
24V
Transition resistance measurement range
1A File:0.8Ω~20Ω
Resolution: 0.1Ω,
Accuracy: ±5% Reading ±0.1Ω
0.2A File:10Ω~100Ω
Transition time measurement range
Sampling rate: 20k, resolution: 0.1ms, accuracy: ±1% reading ±0.2mS
Waveform recording time length
300ms
Dimensions
410mm×320mm×200mm
Weight
About 8kg
 
keywords:
On a
NDBRY-II Transformer low voltage impedance short circuit tester
The next article
NDR series DC resistance tester