Copyright: Wuhan Nanxing Power Technology Co., Ltd.  鄂ICP备06008607号
Website:300.cn  Wuhan

  • 武汉南星电力科技有限公司
  • 武汉南星电力科技有限公司
  • 武汉南星电力科技有限公司

ND-1200 six-phase microcomputer relay protection tester

Profile information:
basic information
Detailed parameters
Categories:
Secondary loop detection class
heat
number:
- +
没有此类产品
Product description
  Reference standard: DL/T624-1997, JJG1112-2015.
 
  Features:
  ● Output up to 6-phase voltage 6-phase current, which can be combined to realize conventional 4-phase voltage 3-phase current type, 6-phase voltage type, 6-phase current type, and 12-phase output mode;
  ● The output part is controlled by DSP, which has fast calculation speed, strong real-time digital signal processing capability, transmission frequency bandwidth and high-resolution D/A conversion. The output waveform has high precision, small distortion and good linearity. It adopts a large number of advanced technologies and precision component materials, and has carried out professional structural design. Therefore, the device is small in size, light in weight, full in function, easy to carry, and can be operated at startup, and the flow test is very convenient;
  ● It can complete large-scale complex verification work with high degree of automation. It can easily test and scan various protection settings, perform fault playback, store test data in real time, display vector graphics, print reports online, etc.
  ● It has one independent 110V and 220V dedicated adjustable DC power supply output, which is convenient for on-site inspection and use;
  ● The new generation ND-1200 tester is equipped with 10-way opening and 8-way opening for easy self-injection test. The input contact is compatible with the 0~250V potential contact, which can be intelligently and automatically recognized.
  ● Provide a variety of automatic test software modules and GPS synchronization trigger test (optional).
 
  The main parameters:
 
AC current source
Range of amplitude
6×(0-30A) Accuracy: ±0.2%+2 words
Output per phase (Effective value) when 6-phase current is output
 0~30A Output accuracy ∠0.2 level (Within the main range)
Output per phase (Effective value) when 3-phase current is output
0~60A
6-phase parallel current output (Effective value)
0~180A
Phase current allowable operating value (effective value) for a long time
10A
Phase current maximum output power efficiency)
80VA
Allowable working time for maximum output of 6-phase parallel current
10s
Frequency range (Fundamental)
0~1000Hz
Harmonic number
0 to 20 Times
DC current source
Current output
0 to ±10A / per phase, 0 to ±60A / 6 
Maximum output load voltage
18V
Precision
Level 0.5
AC voltage source
Phase voltage output (Effective value)
0~120V Output accuracy 0.2 level
Line voltage output (Effective value)
0~240V
Phase voltage / Line voltage output work
80VA / 100VA
Frequency range (Fundamental)
20~1000Hz
Harmonic number
1 to 20 Times
DC voltage source
Phase voltage output amplitude
0~±160V Output accuracy 0.5 level
Line voltage output amplitude
0~±320V
Phase voltage / line voltage output power
70VA / 140VA
Switch
10 Way switch input
Contact
1~20mA,24V
Potential contact
“0”:0 ~ +6V; “1”:+11 V ~ +250V
8 Pairs of digital outputs
DC:220 V/0.2 A;AC:220 V/0.5A
Time measurement
Range
0.1ms ~ 9999s
Measurement accuracy
 <0.1mS
Other
Dimensions
480mm×360mm×200mm
Weight
About 19kg
 
keywords:
On a
ND-802 Three-phase microcomputer relay protection tester